Goodrive35 inverters Function codes
126
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
deviation
limit
%
P09.15
PID
command
of
ACC/DEC
time
0.0~1000.0s
0.0s
P09.16
PID output
filter time
0.000~10.000s
0.000s
P09.17
PID
pre-setting
-100.0~100.0%
0.0%
P09.18
Reserved
0~65536
0
P09.19
Reserved
0~65536
0
P09.20
Reserved
0~65536
0
P10 Group Simple PLC and multi-step speed control
P10.00
Simple
PLC
0: Stop after running once. The inverter has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After
finish a signal, the inverter will keep the running
frequency and direction of the last run.
2: Cycle running. The inverter will keep on running
until receiving a stop command d. And then, the
system will stop.
0
P10.01
Simple
PLC
memory
0: Power loss without memory
1: Power loss memory;PLC record the running stage
and frequency when power loss.
0
P10.02
Multi-step
speed 0
The frequency setting range of stage 0~15:
-100.0~100.0%100.0% of the frequency setting
corresponds to the Max. Frequency P00.03.
0.0%
P10.03
The
0.0s