Goodrive35 inverters Function codes
130
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P10.34
Simple
PLC 0~7
step
ACC/DEC
time
Below is the detailed instruction:
Function
code
Binary bit
Step
ACC/
DEC 0
ACC/
DEC 1
ACC/
DEC 2
ACC/
DEC 3
P10.34
BIT1
BIT0
0
00
01
10
11
BIT3
BIT2
1
00
01
10
11
BIT5
BIT4
2
00
01
10
11
BIT7
BIT6
3
00
01
10
11
BIT9
BIT8
4
00
01
10
11
BIT11
BIT10
5
00
01
10
11
BIT13
BIT12
6
00
01
10
11
BIT15
BIT14
7
00
01
10
11
P10.35
BIT1
BIT0
8
00
01
10
11
BIT3
BIT2
9
00
01
10
11
BIT5
BIT4
10
00
01
10
11
BIT7
BIT6
11
00
01
10
11
BIT9
BIT8
12
00
01
10
11
BIT11
BIT10
13
00
01
10
11
BIT13
BIT12
14
00
01
10
11
BIT15
BIT14
15
00
01
10
11
After users select the corresponding ACC/DEC time,
the combining 16 binary bit can be changed into
hexadecimal bit, and then set the corresponding
function codes.
ACC/DEC time 1 is set by P00.11 and P00.12;
ACC/DEC time 2 is set by P08.00 and P08.01;
ACC/DEC time 3 is set by P08.02 and P08.03;
ACC/DEC time 4 is set by P08.04 and P08.05.
Setting range: 0x0000~0xFFFF
0x000
0
P10.35
Simple
PLC 8~15
step
ACC/DEC
time
0x000
0
P10.36
PLC
restart
0: Restart from the first step; stop during running
(cause by the stop command, fault or power loss),
run from the first stage after restart.
1: Continue to run from the stop frequency; stop
0