Goodrive35 inverters Function codes
131
Detailed instruction of parameters
during running(cause by stop command and fault),
the inverter will record the running time
automatically, enter into the stage after restart and
keep the remaining running at the setting frequency.
0: Seconds;the running time of all steps is counted
by second
1: Minutes;the running time of all steps is counted by
minute
P11 Group Protective parameters
0x00~0x11
LED ones:
0: Input phase loss protection disable
1: Input phase loss protection enable
LED tens:
0: Input phase loss protection disable
1: Input phase loss protection enable
Frequency
-decreasin
g at
sudden
power loss
Frequency
decreasing
ratio at
sudden
power loss
Setting range: 0.00Hz/s~P00.03
(the Max. frequency)
After the power loss of the grid, the bus voltage
drops to the sudden frequency-decreasing point, the
inverter begin to decrease the running frequency at
P11.02, to make the inverter generate power again.
The returning power can maintain the bus voltage to
ensure a rated running of the inverter until the
recovery of power.
Frequency-decre
asing threshold