Goodrive35 inverters Function codes
132
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
1. Adjust the parameter properly to avoid the
stopping caused by inverter protection during the
switching of the grid.
2. Prohibition of input phase loss protection can
enable this function.
P11.03
Overvoltag
e stall
protection
0:Disable
1:Enable
0
P11.04
Voltage
protection
of
overvoltag
e stall
120~150%(standard bus voltage)(380V)
136%
120~150%(standard bus voltage)( 660V)
120%
P11.05
Current
limit action
selection
The actual increasing ratio of motor speed is lower
than the ratio of output frequency because of the big
load during ACC running. It is necessary to take
measures to avoid overcurrent fault and the inverter
trips.
Ones:current limit setting
0:Invalid
1:Valid
1
P11.06
Automatic
current
limit
During the running of the inverter, it will detect the
output current and compare it with the limit level
defined in P11.06. If it exceeds the level, the inverter
will run at stable frequency in ACC running, or the
inverter will derate to run during the constant
160.0
%
P11.07
Frequency
10.00