Goodrive35 inverters Function codes
133
Detailed instruction of parameters
-decreasin
g ratio
during
current
limit
running. If it exceeds the level continuously, the
output frequency will keep on decreasing to the
lower limit. If the output current is detected to be
lower than the limit level, the inverter will accelerate
to run.
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
Overload
pre-alarm
of
motor/inver
ter
The output current of the inverter or the motor is
above P11.09 and the lasting time is beyond P11.10,
overload pre-alarm will be output.
Setting range of P11.08:
Enable and define the overload pre-alarm of the
inverter or the motor.
Setting range: 0x000~0x131
LED ones:
0:Overload pre-alarm of the motor, relative to the
rated current of the motor
1:Overload pre-alarm of the inverter, relative to the
Overload
pre-alarm
detection
Overload
pre-alarm
detection
time