Goodrive35 inverters Function codes
134
Detailed instruction of parameters
rated current of the inverter
LED tens:
0:The inverter continues to work after underload
pre-alarm
1:The inverter continues to work after underload
pre-alarm and the inverter stops to run after overload
fault
2: The inverter continues to work after overload
pre-alarm and the inverter stops to run after
underload fault
LED hundreds :
0:Detection all the time
1:Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~3600.0s
Underload
pre-alarm
detection
If the inverter current or the output current is lower
than P11.11, and its lasting time is beyond P11.12,
the inverter will output underload pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~3600.0s
Underload
pre-alarm
detection
time
Output
terminal
action
during fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x00~0x11
LED ones:
0:Action under fault undervoltage
1:No action under fault undervoltage
LED tens:
0:Action during the automatic reset
1:No action during the automatic reset
0.0~50.0%
Set the speed deviation detection time