Goodrive35 inverters Basic operation instruction
174
issue.
Besides P00.01 and P00.02, terminal command setting can also used to set the running command
channel.
Current running
command
channel
P00.01
Multi-function
terminal 36
Switch to keypad
Multi-function
terminal 37
Switch to terminal
Multi-function
terminal 38
Switch to
communication
Keypad running
command channel
/
Terminal running
command channel
Communication
running command
channel
Terminal running
command channel
Keypad running
command channel
/
Communication
running command
channel
Communication
running command
channel
Keypad running
command channel
Terminal running
command channel
/
Note: / means the multi-function terminal is invalid on the current given channel.
Relative parameters table:
Function
code
Name
Detailed instruction of parameters
Default
value
P00.00
Speed control mode
0: Sensorless vector control mode 0
(apply to AM and SM)
1: Sensorless vector control mode 1
(applying to AM)
2:SVPWM control
2
P00.01
Run command channel
0:Keypad running command
1:Terminal running command channel
(“LOCAL/REMOT” flickering)
2:Communication running command
channel (“LOCAL/REMOT” on);
0
P00.02
Communication running
commands
0:MODBUS communication channel
1: PROFIBUS\CANopen communication
channel
2:Ethernet communication channel
0