Goodrive35 inverters Basic operation instruction
197
during normal powering on, start after the restarting function becomes valid during normal
powering on and start after the automatic fault reset. Below is the detailed instruction for three
starting.
There are three starting modes for the inverter: start from the starting frequency directly, start after
the AC braking and start after the rotation speed tracking. The user can select according to
different situations to meet their needs.
For the load with big inertia, especially in the cases where the reverse rotation may occur, it is
better to select starting after DC braking and then starting after rotation speed tracking.
Note: It is recommended to use the direct starting to drive synchronous motor.
The starting logic figure of starting after the running command during the normal powering on.
Jogging running
N
1f
1t
P00.11
ACC time
P00.12
DEC time
ACC
DEC
P00.03
ACC
DEC
P00.03
1f
1t
P08.07
ACC time
P08.08
DEC time
ACC
DEC
P08.06
1t
1f
1t
Jumping
frequency 2
1/2*jumping range 2
1/2*jumping range 2
Jumping
frequency1
1/2*jumping range 1
1/2*jumping range 1
Jumping
frequency3
1/2*jumping range 3
1/2*jumping range 3
Y
Start after rotation speed tracking
P01.00
Starting running
Start directly
The starting frequency
The starting frequency
The retention time
The braking time before starting
The braking current before starting
P01.05
ACC/DEC method selection
P00.11
ACC time
P00.12
DEC time
0
1
2
0
1
Linear ACC/DEC
S curve ACC/DEC
Start directly
Start after DC braking
Jogging running frequency
1f
2. The starting logic figure of starting after the restarting function becomes valid during the normal
powering on.
Stand by
The running state before
power off
0
1
P01.21
restarting after the power off
selection
The waiting time of the restarting
after power off >P01.22
0
1
2
stopping
Running
0
1
P01.18
(the running protection of the powering on
terminal selection)
The retention time of the
restarting
>P01.123
N
Y
Y
N
Restart after
the power off
Running
Stoppin
g
FWD/REV
Whether the running command terminal
is valid
N
Running
Y
P00.01
Running command channel
Keypad
Comm
unicati
on
Terminal
www.barghmaher.ir

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive 35 Series and is the answer not in the manual?

INVT Goodrive 35 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive 35 Series
CategoryInverter
LanguageEnglish

Related product manuals