Goodrive35 inverters Basic operation instruction
208
0
1
2
3
.
.
.
.
.
.
19
20
P06.14
P06.15
P06.16
AO1
AO2
HDO
P06.17
P06.18
P06.19
P06.20
P06.22
P06.23
P06.24
P06.25
P06.27
P06.28
P06.29
P06.30
P06.26
P06.21
P06.31
(default value is 0)
(default value is 0)
(default value is 0)
P06.00
( HDO output type selection(
0 Running frequency 1 Set frequency
3 Running rotation speed 4 Output current (relative to the inverter)
6 Output voltage 7 Output power
9 Output torque 10 Analog AI1 input value
12 Analog AI3 input value 13 HDI input value
15 MODBUS communication setting 2 16 PROFIBUS communication setting 1
2 Ramp given frequency
5 Output current (relative to the motor)
8 Set torque
11 Analog AI2 input value
14 MODBUS communication setting 1
17 PROFIBUS communication setting 1
18
Torque current (relative to the nominal
current of the motor)
19
Exciting current (relative to the nominal
current of the motor)
20 Reserved
0
1
P06.00
0: open collector high speed pulse
output
1: open collector output
P06.01( P06.02( P06.03( P06.04 output selection
Analog output curve setting
Analog output selection Analog output filter setting
Output instructions:
Set value
Function
Instructions
0
Running frequency
0~ the Max. output frequency
1
Set frequency
0~ the Max. output frequency
2
Ramp given frequency
0~ the Max. output frequency
3
Running speed
0~2 times of the rated synchronous rotation speed of
the motor
4
Output current
(relative to the inverter)
0~2 times of the rated current of the inverter
5
Output current (relative to the
motor)
0~2 times of the rated current of the inverter
6
Output voltage
0~1.5 times of the rated voltage of the inverter
7
Output power
0~2 times of the rated power
8
Setting torque value
0~2 times of the rated current of the motor
9
Output torque
0~2 times of the rated current of the motor
10
AI1
0~10V/0~20mA
11
AI2
0~10V/0~20mA
12
AI3
-10V~10V
13
HDI
0.00~50.00kHz
14
Setting value 1 of MODBUS
-1000~1000,1000 corresponds to 100.0%
www.barghmaher.ir

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive 35 Series and is the answer not in the manual?

INVT Goodrive 35 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive 35 Series
CategoryInverter
LanguageEnglish

Related product manuals