Goodrive35 inverters Fault tracking
249
The voltage of the power
supply is too low
The motor setting rated
current is incorrect
The motor stall or load
transients is too strong
Check the power of the supply
line
Reset the rated current of the
motor
Check the load and adjust the
torque lift
The acceleration is too fast
Reset the rotating motor
The voltage of the power
supply is too low.
The load is too heavy.
The motor power is too
small.
Increase the ACC time
Avoid the restarting after
stopping.
Check the power of the supply
line
Select an inverter with bigger
power.
Select a proper motor.
The inverter will report
overload pre-alarm
according to the set value.
Check the load and the overload
pre-alarm point.
Phase loss or fluctuation of
input R,S,T
Check input power
Check installation distribution
U,V,W phase loss input(or
serious asymmetrical three
phase of the load)
Check the output distribution
Check the motor and cable
Rectifying
module
overheated
Air duct jam or fan damage
Ambient temperature is too
high.
The time of overload running
is too long.
Refer to the overcurrent solution
Redistribute dredge the wind
channel or change the fan
Low the ambient temperature
Check and reconnect
Change the power
Change the power unit
Change the main control panel
SI external fault input
terminals action
Check the external device input