293
Available Not available (with interference to the keypad wiring)
Repeater
Up to 32 stations can be connected to each segment (master station or subsidiary stations),
the repeater have to be used when stations is more than 32. The repeaters in series are
generally no more than 3.
Note: There is no repeater station address.
A.2.6.4 Transmission rate and maximum distance
Maximum length of cable depends on the transmission rate. The Table below shows the
relationship between transmission rate and distance.
Transmission rate (kbps)
A-wire (m)
B-wire (m)
9.6
1200
1200
19.2
1200
1200
93.75
1200
1200
187.5
1000
600
500
400
200
1500
200
-----
12000
100
-----
Transmission line parameters: