Goodrive35 inverters                                                                                              Appendix A                                                                                                         
294 
Capacitance per unit length(pF/m) 
Line-core cross-section (mm
2
) 
Besides  shielding twisted-pair copper wires, PROFIBUS/CANOPEN can also use optical 
fiber  for  transmission  in  an  electromagnetic  interference  environment  to  increase  the 
high-speed transmission  distance  there are  two  kinds of  fiber optical  conductors,  one is 
low-cost plastic fiber conductor, used distance is less than 50 meters, the other is glass fiber 
conductor, and used distance is less than 1 kM. 
A.2.6.5 PROFIBUS/CANOPEN bus connection diagram 
 
Above  is  "terminal"  wiring  diagram.  Cable  is  a  standard  PROFIBUS/CANOPEN  cable 
consisting of a twisted pair and shielding layer. The shielded layer of PROFIBUS/CANOPEN 
cable  on  all  nodes  is  directly  grounded.  Users  can  choose  the  best  grounding  method 
according to the situation.   
Note:     
Make sure that signal lines do not twist when connecting all stations. Shielded cable should 
be used when system runs under high electromagnetic interface environment, which can 
improve electromagnetic compatibility (EMC).   
If using shielded braided wire and shielding foil, both ends should be connected to ground. 
Using shielding area should be large enough to maintain a good conductivity. And data lines 
must be separated from high-voltage.   
Stub line segment should not be used when transmission rate more than 500K bit/s, The 
plug is available on the market which connects directly to data input and output cable. Bus 
plug connection can be on or off at any time without interruption of data communications of