Goodrive35 inverters Appendix A
295
other station.
A.2.7 System configuration
1. Master station and inverter should be configured so that the master station can
communicate with the module after correctly installing EC-TX-103 communication card.
Each PROFIBUS/CANOPEN subsidiary station on the PROFIBUS/CANOPEN bus need to
have "device description document" named GSD file which used to describe the
characteristics of PROFIBUS/CANOPEN-DP devices. The software we provided for the user
includes inverter related GSD files (device data files) information, users can obtain type
definition file (GSD) of master machines from local INVT agent.
Configuration parameters of EC-TX-103 communication card:
Parameter number
Parameter name
Optional setting
Factory setting
0
Module type
Read only
PROFIBUS/CANOP
EN-DP
1
Node address
0~99
2
2
Baud rate setting
kbit/s
0:9.6
6
1:19.2
2:45.45
3:93.75
4:187.5
5:500
Mbit/s
6:1.5
7:3
8:6
9:9
10:12
3
PZD3
0~65535
0
4
PZD4
Ibid
0
……
Ibid
0
10
PZD12
Ibid
0
2. Module type
This parameter shows communication module type detected by inverter; users can not
adjust this parameter. If this parameter is not defined, communication between the modules
and inverter can not be established.