3: Close loop vector control
Need to install encoders. It is suitable in cases with
low frequency, high speed control accuracy for
accurate speed and torque control.
Note: AM-Asynchronous motor
SM-Synchronous motor
Select the run command channel of the inverter.
The control command of the inverter includes:
start-up, stop, forward, reverse, jogging and fault
reset.
0:Keypad running command
channel(“LOCAL/REMOT” light off)
Carry out the command control by RUN, STOP/RST
on the keypad.
Set the multi-function key QUICK/JOG to
FWD/REVC shifting function (P07.02=3) to change
the running direction; press RUN and STOP/RST
simultaneously in running state to make the inverter
coast to stop.
1:Terminal running command channel
(“LOCAL/REMOT” flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi-function
terminals
2:Communication running command channel
(“LOCAL/REMOT” on);
The running command is controlled by the upper
monitor via communication
Select the controlling communication command
channel of the inverter.
0: MODBUS communication channel
1: PROFIBUS\CANopen communication channel
2: Ethernet communication channel