Goodrive35 inverters Function codes
64
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
frequency.
Setting range: 0.0~50.0s
P01.03
The
braking
current
before
starting
The inverter will carry out DC braking at the braking
current set before starting and it will speed up after
the DC braking time. If the DC braking time is set to
0, the DC braking is invalid.
The stronger the braking current, the bigger the
braking power. The DC braking current before
starting means the percentage of the rated current of
the inverter.
The setting range of P01.03: 0.0~100.0%
The setting range of P01.04: 0.0~30.0s
0.0%
P01.04
The
braking
time before
starting
0.0s
P01.05
ACC/DEC
selection
The changing mode of the frequency during start-up
and running.
0:Linear type
The output frequency increases or decreases
linearly.
1: S curve
0
P01.06
ACC time
0.0~50.0s