Goodrive35 inverters Function codes
63
Detailed instruction of parameters
Function
restore
parameter
0:No operation
1:Restore the default value
2:Cancel the fault record
Note: The function code will restore to 0 after
finishing the operation of the selected function code.
Restoring to the default value will cancel the user
password, please use this function with caution.
P01 Group Start-up and stop control
0:Start-up directly:start from the starting frequency
P01.01
1:Start-up after DC braking: start the motor from the
starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in the
cases where reverse rotation may occur to the low
inertia load during starting.
2: Start-up after speed tracing: start the rotating
motor smoothly after tracking the rotation speed and
direction automatically. It is suitable in the cases
where reverse rotation may occur to the big inertia
load during starting.
Note: The inverters above 4kW have the function.
Starting
frequency
of direct
start
Starting frequency of direct start-up means the
original frequency during the inverter starting. See
P01.02 for detailed information.
Setting range: 0.00~50.00Hz
Retention
time of the
starting
frequency
Set a proper starting frequency to increase the
torque of the inverter during starting. During the
retention time of the starting frequency, the output
frequency of the inverter is the starting frequency.
And then, the inverter will run from the starting
frequency to the set frequency. If the set frequency is
lower than the starting frequency, the inverter will
stop running and keep in the stand-by state. The
starting frequency is not limited in the lower limit