Goodrive35 inverters Function codes
62
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
temperature and the impact to the output capacity.
The inverter needs to derate on high carrier
frequency. At the same time, the leakage and
electrical magnetic interference will increase.
Applying low carrier frequency is contrary to the
above, too low carrier frequency will cause unstable
running, torque decreasing and surge.
The manufacturer has set a reasonable carrier
frequency when the inverter is in factory. In general,
users do not need to change the parameter.
When the frequency used exceeds the default
carrier frequency, the inverter needs to derate 10%
for each additional 1k carrier frequency.
Setting range: 1.2~15.0kHz
P00.15
Motor
parameter
autotuning
0:No operation
1:Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning when
high control accuracy is needed.
2: Static autotuning 1(autotune totally); It is suitable
in the cases when the motor can not de-couple from
the load. The antotuning for the motor parameter will
impact the control accuracy.
3: Static autotuning 2(autotune part parameters);
when the current motor is motor 1, autotune P02.06,
P02.07, P02.08; and when the current motor is
motor 2, autotune P12.06, P12.07, P12.08.
0
P00.16
AVR
function
selection
0:Invalid
1:Valid during the whole procedure
The auto-adjusting function of the inverter can
cancel the impact on the output voltage of the
inverter because of the bus voltage fluctuation.
1
P00.17
Reserved
Reserved
0