Goodrive35 inverters Function codes
68
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
3: Run at zero frequency
The inverter will coast to stop when the set
frequency is lower than the lower-limit one. If the set
frequency is above the lower limit one again and it
lasts for the time set by P01.20, the inverter will
come back to the running state automatically.
P01.20
Hibernatio
n restore
delay time
This function code determines the hibernation delay
time. When the running frequency of the inverter is
lower than the lower limit one, the inverter will pause
to stand by.
When the set frequency is above the lower limit one
again and it lasts for the time set by P01.20, the
inverter will run automatically.
Note: The time is the total value when the set
frequency is above the lower limit one.
Setting range: 0.0~3600.0s (valid when P01.19=2)
0.0s
P01.21
Restart
after power
off
This function can enable the inverter start or not after
the power off and then power on.
0: Disable
1: Enable, if the starting need is met, the inverter will
run automatically after waiting for the time defined by
P01.22.
0
P01.22
The
waiting
time of
restart
after power
The function determines the waiting time before the
automatic running of the inverter when powering off
and then powering on.
1.0s