Goodrive35 inverters Function codes
76
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
The setting range of P03.04:0.000~10.000s
The setting range of P03.05:P03.02~P00.03(the
Max. output frequency)
P03.06
Speed
loop output
filter
0~8 (corresponds to 0~2
8
/10ms)
0
P03.07
Compensa
tion
coefficient
of
electromoti
on slip
Slip compensation coefficient is used to adjust the
slip frequency of the vector control and improve the
speed control accuracy of the system. Adjusting the
parameter properly can control the speed
steady-state error.
Setting range:50%~200%
100%
P03.08
Compensa
tion
coefficient
of braking
slip
100%
P03.09
Current
loop
percentage
coefficient
P
Note:
1 These two parameters adjust the PI adjustment
parameter of the current loop which affects the
dynamic response speed and control accuracy
directly. Generally, users do not need to change the
default value.
2 Only apply to the vector control mode without PG
0(P00.00=0).
Setting range: 0~20000
1000
P03.10
Current
loop
integral
coefficient
1
1000
P03.11
Torque
setting
method
This parameter is used to enable the torque control
mode, and set the torque.
0:Torque control is invalid
1:Keypad setting torque(P03.12)
2:Analog AI1 setting torque
3:Analog AI2 setting torque
4:Analog AI3 setting torque
0