Goodrive35 inverters Function codes
77
Detailed instruction of parameters
5:Pulse frequency HDI setting torque
6:Multi-step torque setting
7:MODBUS communication setting torque
8:PROFIBUS\CANopen communication setting
torque
9:Ethernet communication setting torque
10:Reserved
Note: Setting modes 2~10, 100% corresponds to
three times of the rated current of the motor.
Setting range: -300.0%~300.0%(rated current of the
motor)
Torque
reference
filter time
Upper
frequency
of forward
rotation in
vector
control
0:Keypad (P03.16 sets P03.14,P03.17 sets P03.15)
1: AI1
2: AI2
3: AI3
4:Pulse frequency HDI setting upper-limit frequency
5:Multi-step setting upper-limit frequency
6:MODBUS communication setting upper-limit
frequency
7:PROFIBUS/CANopen communication setting
upper-limit frequency
8:Ethernet communication setting upper-limit
frequency
Note:Setting method 1~8, 100% corresponds to the
maximum frequency
Upper
frequency
of reverse
rotation in
vector
control
This function is used to set the upper limit of the
frequency. P03.16 determines the setting when
P03.14=1; P03.17 determines the setting when