Goodrive35 inverters Function codes
77
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
5:Pulse frequency HDI setting torque
6:Multi-step torque setting
7:MODBUS communication setting torque
8:PROFIBUS\CANopen communication setting
torque
9:Ethernet communication setting torque
10:Reserved
Note: Setting modes 2~10, 100% corresponds to
three times of the rated current of the motor.
P03.12
Keypad
setting
torque
Setting range: -300.0%~300.0%(rated current of the
motor)
10.0%
P03.13
Torque
reference
filter time
0.000~10.000s
0.100s
P03.14
Upper
frequency
of forward
rotation in
vector
control
0:Keypad (P03.16 sets P03.14,P03.17 sets P03.15)
1: AI1
2: AI2
3: AI3
4:Pulse frequency HDI setting upper-limit frequency
5:Multi-step setting upper-limit frequency
6:MODBUS communication setting upper-limit
frequency
7:PROFIBUS/CANopen communication setting
upper-limit frequency
8:Ethernet communication setting upper-limit
frequency
Note:Setting method 1~8, 100% corresponds to the
maximum frequency
0
P03.15
Upper
frequency
of reverse
rotation in
vector
control
0
P03.16
Keypad
setting for
upper
This function is used to set the upper limit of the
frequency. P03.16 determines the setting when
P03.14=1; P03.17 determines the setting when
50.00
Hz
www.barghmaher.ir