Goodrive35 inverters Function codes
86
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
control
threshold
of motor 2
Hz
P04.26
Energy-sa
ving
operation
0:No operation
1:Automatic energy-saving operation (reserved)
Motors will automatically adjust the output voltage to
save energy when light loads.
0
P04.27
Voltage
setting
Select the output setting channel at V/F curve
separation.
0: Keypad: the output voltage is determined by
P04.28.
1:AI1 ;
2:AI2;
3:AI3;
4:HDI;
5:Multi-step speed;
6:PID;
7:MODBUS communication;
8:PROFIBUS/CANopen communication;
9:Ethernet communication;
10: Reserved
Note: 100% corresponds to the rated voltage of the
motor.
0
P04.28
Keypad
setting
voltage
The function code is the voltage displaying when the
voltage is set through keypad.
The setting range:0.0%~100.0%
100.0
%
P04.29
Voltage
increasing
time
Voltage increasing time is the time when the inverter
accelerates from the output minimum voltage to the
output maximum voltage.
Voltage decreasing time is the time when the inverter
decelerates from the output maximum voltage to the
output minimum voltage.
The setting range:0.0~3600.0s
5.0s
P04.30
Voltage
decreasing
time
5.0s
P04.31
Maximum
Set the upper and low limit of the output voltage.
100.0
www.barghmaher.ir