The function code defines the relationship between
the analog input voltage and its corresponding set
value. If the analog input voltage beyond the set
minimum or maximum input value, the inverter will
count at the minimum or maximum one.
When the analog input is the current input, the
corresponding voltage of 0~20mA is 0~10V.
In different cases, the corresponding rated value of
100.0% is different. See the application for detailed
information.
The figure below illustrates different applications:
Input filter time: this parameter is used to adjust the
sensitivity of the analog input. Increasing the value
properly can enhance the anti-interference of the
analog, but weaken the sensitivity of the analog
input.
Note: Analog AI1 and AI2 can support 0~10V or
0~20mA input, when AI1 and AI2 selects 0~20mA
input, the corresponding voltage of 20mA is 5V. AI3
can support the output of -10V~+10V.
The setting range of P05.32:0.00V~P05.34
The setting range of P05.33: -300.0%~300.0%