Goodrive270 series VFD for fan and pump Basic operation guidelines
-92-
(2) Logic diagram for start after power-off restart is effective
Standby
Run status
before power failure
0
1
P01.21
(restart at power-off)
Waiting time of restart at
power-off>P01.22
0
1
2
Stop
Run
0
1
P01.18
(Power-on terminal running protection
selection)
Delay time of restart
>P01.23
N
Y
Y
N
Restart after
power-off
Run
Stop
Whether FWD/REV
running terminal command
is valid
N
Run
Y
P00.01
Running command channel
Keypad
Communi
cation
Terminal
(3) Logic diagram for start after automatic fault reset
VFD fault
In running
Automatic reset times
of VFD fault<P08.28
Automatic reset
interval of VFD
fault>P08.29
Restart after VFD
fault reset
Display the fault
code and stop
N
N
Y
Y
Related parameter list:
Function
code
Name
Description
Default
P00.01
Channel of running
commands
0: Keypad
1: Terminal
2: Communication
0
P00.11
ACC time 1
0.0–3600.0s
Depends
on model
P00.12
DEC time 1
0.0–3600.0s
Depends
on model
P01.00
Start mode
0: Direct start
1: Start after DC braking
2: Speed tracking restart
Note: For AMs, speed tracking is not
supported in SVC 0, and software speed
tracking is supported in other modes. For
details, see parameters P01.35–P01.41.
0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals