Goodrive270 series VFD for fan and pump Basic operation guidelines
-139-
variable-frequency
motor adding
Variable-frequency
motor DEC time for
power-frequency
motor adding
Pressure tolerance
for motor reducing
0.0–30.0% (relative to PID1 max. value)
Running frequency
for motor reducing
P00.05–P94.20 (Running frequency for
motor adding)
Variable-frequency
motor action for
motor reducing
0: Keep the frequency unchanged
1: Accelerate to the motor running
frequency
Variable-frequency
motor ACC time for
motor reducing
5.5.16.2 Polling function
Automatic polling
The VFD supports the automatic water pump polling function to achieve two goals: First, to keep the
run time of each pump the same to balance the loss; Second, to prevent any pump from stopping for
too long, which could lead to blocking.
When the initial motor running time exceeds P94.34 (Variable-frequency motor polling cycle) and the
present frequency is higher than P94.35 (Polling running frequency threshold), the VFD starts
automatic polling. It changes the objects of variable-frequency control objects by adding and reducing
motors and then re-calculates the polling time.
Note: Polling time recalculation is also triggered by motor adding or reducing that occurs during
normal PID adjustment.
Related parameter list:
0.0–6000.0h
Automatic polling is targeted at idle
variable-frequency motors. The value 0
indicates no polling.