Goodrive270 series VFD for fan and pump Function parameter list
-151-
When the set frequency is higher than the upper
limit of the running frequency, the upper limit of
the running frequency is used for running.
Setting range: P00.05–P00.03 (Max. output
frequency)
Lower limit of
running frequency
The lower limit of the running frequency is the
lower limit of the output frequency of the VFD,
When the set frequency is lower than the lower
limit of the running frequency, the lower limit of
the running frequency is used for running.
Note: Max. output frequency ≥ Upper limit of
frequency ≥ Lower limit of frequency
Setting range: 0.00Hz–P00.04 (Upper limit of
running frequency)
Setting channel of A
frequency
command
0: Keypad
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: Modbus communication
9: PROFIBUS/CANopen communication
10: Ethernet communication
11: Reserved
12: Reserved
13: PROFINET communication
14–17: Reserved
18: Keypad (for small power models)
Setting channel of B
frequency
command
Reference object of
B frequency
command
0: Max. output frequency
1: A frequency command
Combination mode
of setting source
0: A
1: B
2: (A+B)
3: (A-B)
4: Max(A, B)