Goodrive270 series VFD for fan and pump Function parameter list
-175-
space voltage vector mode, and thus improve
the rigidity of the mechanical characteristics of
the motor. You need to calculate the rated slip
frequency of the motor as follows:
△ f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor
2, corresponding to function code P12.02. n is
the rated rotating speed of the motor 2,
corresponding to function code P12.03. p is the
number of pole pairs of the motor. 100.0%
corresponds to the rated slip frequency △ f of
motor 2.
Setting range: 0.0–200.0%
Low-frequency
oscillation control
factor of motor 2
In space voltage vector control mode, the motor,
especially the large-power motor, may
experience current oscillation at certain
frequencies, which may cause unstable motor
running, or even VFD overcurrent. You can
adjust the two function codes properly to
eliminate such phenomenon.
P04.23 setting range: 0–100
P04.24 setting range: 0–100
P04.25 setting range: 0.00Hz–P00.03 (Max.
output frequency)
High-frequency
oscillation control
factor of motor 2
Oscillation control
threshold of motor 2
0: Disable
1: Automatic energy-saving run
In light-load state, the motor can adjust the
output voltage automatically to achieve energy
saving.
0: Keypad (The output voltage is determined by
P04.28.)
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step speed running (The setting is
determined by group P10.)
6: PID