Sin: Three-wire control; FWD: Forward running;
REV: Reverse running
Note: For two-wire controlled running mode, when
the FWD/REV terminal is valid, if the VFD stops
due to a stop command given by another source,
the VFD does not run again after the stop
command disappears even if the control terminal
FWD/REV is still valid. To make the VFD run, you
need to trigger FWD/REV again, for example, PLC
single-cycle stop, fixed-length stop, and valid
STOP/RST stop during terminal control. (See
P07.04.)
Used to specify the delay time corresponding to
the electrical level changes when the
programmable input terminals switch on or switch
off.
Setting range: 0.000–50.000s
Note: After a virtual terminal is enabled, the state
of the terminal can be changed only in
communication mode. The communication
address is 0x200A.