Goodrive270 series VFD for fan and pump Function parameter list
-193-
Function
code
Name
Description
Default
Modify
completed, the parameter restores to 0. The
upload and download functions are not
applicable to group P29.
P07.02
Key function
selection
Range: 0x000x27
Ones place: Function of QUICK/JOG
0: No function
1: Jog
2: Reserved
3: Switch between forward and reverse rotating
4: Clear the UP/DOWN setting
5: Coast to stop
6: Switch command channels in sequence
7: Reserved
Tens place: Reserved
0x01
P07.03
Sequence of
switching
running-command
channels by
pressing QUICK
When P07.02=6, set the sequence of switching
running-command channels by pressing this
key.
0: Keypad→Terminal→Communication
1: Keypad←→Terminal
2: Keypad←→Communication
3: Terminal←→Communication
0
P07.04
Stop function
validity of
STOP/RST
Used to specify the stop function validity of
STOP/RST. For fault reset, STOP/RST is valid
in any conditions.
0: Valid only for keypad control
1: Valid both for keypad and terminal control
2: Valid both for keypad and communication
control
3: Valid for all control modes
0
P07.05
Selection 1 of
parameters
displayed in running
state
0x00000xFFFF
Bit 0: Running frequency (Hz on)
Bit 1: Set frequency (Hz blinking)
Bit 2: Bus voltage (V on)
Bit 3: Output voltage (V on)
Bit 4: Output current (A on)
Bit 5: Running speed (RPM on)
Bit 6: Output power (% on)
Bit 7: Output torque (% on)
0x03FF

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals