EasyManua.ls Logo

INVT Goodrive270 Series - Page 231

INVT Goodrive270 Series
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive270 series VFD for fan and pump Function parameter list
-221-
Function
code
Name
Description
Default
Modify
P11.29
Software input
phase loss
detection limit value
0200.0V
40.0V
P11.30
Software input
phase loss
detection time
020.0s
2.0s
P11.31
Fault protection
selection 1
0x00000x3313
LED ones place: Motor overload
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
LED tens place: VFD overload
0: Coast to stop
1: Stop according to the stop mode
LED hundreds place: Input phase loss (same as
that for ones place)
LED thousands place: Output phase loss on
output side (same as that for ones place)
0x0000
P11.32
Fault protection
selection 2
0x00000x3300
LED ones place: Rectifier module overheating
0: Coast to stop
LED tens place: Inverter module overheat (same
as that for ones place)
LED hundreds place: External fault
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
LED thousands place: RS485 communication
fault (same as that for hundreds place)
0x0000
P11.33
Fault protection
selection 3
0x00000x3100
LED ones place: Current detection fault
0: Coast to stop
LED tens place: Motor autotuning fault (same as
that for ones place)
LED hundreds place: EEPROM operation fault
0: Coast to stop
0x0000

Table of Contents

Related product manuals