Goodrive270 series VFD for fan and pump Function parameter list
-222-
Function
code
Name
Description
Default
Modify
1: Stop according to the stop mode
LED thousands place: PID feedback offline
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
P11.34
Fault protection
selection 4
0x0000–0x1311
Ones place: Reserved
0: Reserved
1: Reserved
Tens place: Running time reached (same as that
for ones place)
0: Coast to stop
1: Stop according to the stop mode
Hundreds place: Electronic overload
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
Thousands place: Keypad communication fault
(same as that for ones place)
0x0000
â—‹
P11.35
Fault protection
selection 5
0x0000–0x0300
Ones place: Keypad upload fault
0: Coast to stop
Tens place: Keypad download fault (same as
that for ones place)
Hundreds place: DP communication fault
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
Thousands place: Reserved
0x0000
â—‹
P11.36
Fault protection
selection 6
0x0000–0x3003
Ones place: CANopen communication fault
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
0x0000
â—‹

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals