Goodrive270 series VFD for fan and pump Function parameter list
-223-
Function
code
Name
Description
Default
Modify
Tens place: To-ground short-circuit fault 1
0: Coast to stop
Hundreds place: To-ground short-circuit fault 2
(same as that for tens place)
Thousands place: Speed deviation fault (same
as that for ones place)
P11.37
Fault protection
selection 7
0x00000x0011
Ones place: Mal-adjustment fault
0: Coast to stop
1: Stop according to the stop mode
Tens place: Electronic underload fault (same as
that for ones place)
Hundreds place: Reserved
Thousands place: Reserved
0x0000
P11.38
Fault protection
selection 8
Reserved
P11.39
Fault protection
selection 9
Reserved
P11.40
Fault protection
selection 10
Reserved
P11.41
Fault protection
selection 11
Reserved
P11.42
Fault protection
selection 12
0x00000x3303
Ones place: Duplicate expansion card type
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
Tens place: Reserved
Hundreds place: PROFINET communication
timeout fault (same as that for ones place)
Thousands place: CAN communication fault
(same as that for ones place)
0x0000
P11.43
Fault protection
selection 13
0x00000x0333
Ones place: Motor overheating
0: Coast to stop
1: Stop according to the stop mode
0x0000