Goodrive270 series VFD for fan and pump Function parameter list
-224-
Function
code
Name
Description
Default
Modify
Tens place: Failed to identify the expansion card
in card slot 1
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
Hundreds place: Failed to identify the expansion
card in card slot 2 (same as that for tens place)
Thousands place: Reserved
P11.44
Fault protection
selection 14
0x00000x0033
Ones place: Communication timeout of
expansion card at card slot 1
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
Tens place: Communication timeout of
expansion card at card slot 2 (same as that for
ones place)
Hundreds place: Reserved
Thousands place: Reserved
0x0000
P11.45
Fault protection
selection 15
0x00000x0300
Ones place: Reserved
Tens place: Reserved
Hundreds place: CAN slave fault in master/slave
synchrization
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
3: Keep running
Thousands place: Reserved
0x0000
P11.46
Fault protection
selection 16
0x00000x3300
Ones place: Reserved
Tens place: Reserved
Hundreds place: Freezing fault
0: Coast to stop
1: Stop according to the stop mode
2: Pre-alarm and run
0x0000