Goodrive270 series VFD for fan and pump Function parameter list
-264-
Function
code
Name
Description
Default
Modify
P96.13
Low-temperature
pre-alarm threshold
-20.0°C 20.0°C
When the temperature is lower than the value of
this function code, the pre-alarm terminal
outputs a signal.
0.0°C
P96.14
Freezing protection
frequency
0.0P00.04
0.0Hz
P96.15
Current of triggering
condensation
protection
0.0100.0%
When an external terminal triggers the
condensation protection signal, the VFD
transfers DC current and stops the transfer if the
duration reaches 40s. The condensation
protection signal needs to be triggered again.
30.0%
P96.16
P96.19
Reserved
P96.20
Forward run
frequency for pump
cleaning
0.00HzP00.04
50.00Hz
P96.21
Reverse run
frequency for pump
cleaning
0.00HzP00.04
50.00Hz
P96.22
Forward run ACC
time for pump
cleaning
0.03600.0s
5.0s
P96.23
Reverse run ACC
time for pump
cleaning
0.03600.0s
5.0s
P96.24
Forward run
duration for pump
cleaning
0.03600.0s
5.0s
P96.25
Reverse run
duration for pump
cleaning
0.03600.0s
5.0s
P96.26
Forward/reverse
run interval for
pump cleaning
0.03600.0s
1.0s
P96.27
Number of pump
cleaning cycles
11000
1