P96.28
Motor stalling
function selection
Prerequisite for selecting the function: The VFD
exceeds the stalling current limit, the output
frequency is lower than the stalling frequency
upper limit, and the duration of this situation
exceeds the stalling time.
0: Disable
1: Alarm
2: Faulty
0
â—‹
P96.29
Stalling current limit
0.0–1600.0%
Note: 100.0% corresponds to the motor rated
current.
200.0%
â—‹
P96.30
Stalling frequency
upper limit
0.00–P00.06
It cannot be lower than 10Hz.
15Hz
â—‹
P96.31
Stalling detection
time
0.0–3600.0s
2.0s
â—‹
P96.32
Motor dry pumping
function selection
0: Disable
1: Alarm
2: Faulty
0
â—‹
P96.33
Current limit for
motor dry pumping
0.0%–100.0%
Note: 100.0% corresponds to the motor rated
current.
0.0%
â—‹
P96.34
Detection time for
motor dry pumping
0.0–3600.0s
2.0s
â—‹
P96.35
Motor
overtemperature
point
When the detected motor temperature is higher
than the value of this function code, a fault is
reported.
110.0°

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals