Goodrive270 series VFD for fan and pump Function parameter list
-265-
Motor stalling
function selection
Prerequisite for selecting the function: The VFD
exceeds the stalling current limit, the output
frequency is lower than the stalling frequency
upper limit, and the duration of this situation
exceeds the stalling time.
0: Disable
1: Alarm
2: Faulty
0.0–1600.0%
Note: 100.0% corresponds to the motor rated
current.
Stalling frequency
upper limit
0.00–P00.06
It cannot be lower than 10Hz.
Motor dry pumping
function selection
0: Disable
1: Alarm
2: Faulty
Current limit for
motor dry pumping
0.0%–100.0%
Note: 100.0% corresponds to the motor rated
current.
Detection time for
motor dry pumping
Motor
overtemperature
point
When the detected motor temperature is higher
than the value of this function code, a fault is
reported.