To remove the HYDROVAR – cover, the 4 fastening screws must be opened.
o Ensure that there is no water on the unit before you open the cover.
The HYDROVAR has to be positioned on the motor fan cover (check if the mounting of
the motor fan cover is done properly).
Try to centre it as good as possible using the rubber centre bit.
o
If the HYDROVAR is mounted on a motor with plastic fan cover, a stainless steel
mounting ring must be used.
The HYDROVAR is installed on the motor fan cover by using the mounting brackets, the
four screws and the related washers.
The HYDROVAR has to be centred and then the four screws must be tightened.
Tighten each fastening screw until the two bottom teeth in the brackets start to grip the
fan cover.
After the electrical components are connected, the top cover on the HYDROVAR can be
mounted and tightened by the four fastening screws.
o Make sure of a good connection of the ground wire.
o Control the gasket of the HYDROVAR before tighten the fastening screws.
o Ensure that the mounting of the cable glands is done properly and use closing
glands for cable-bushings which aren’t used.