EasyManuals Logo

ITT HYDROVAR Series User Manual

ITT HYDROVAR Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #65 background imageLoading...
Page #65 background image
64
0215
0215 RAMP 1
4 Sec
Ramp 1: Fast acceleration time
Possible settings: 1 – 250 sec
o Excessively fast running up time may cause an error (OVERLOAD) during the HYDROVAR
starts up.
o Excessively slow running up time may cause a drop of the outgoing pressure during
operation.
0220
0220 RAMP 2
4 Sec
Ramp 2: Fast deceleration time
Possible settings: 1 – 250 sec
o Excessively fast running down time tends to cause an error (OVERVOLTAGE)
o Excessively slow running down time tends to generate over pressure.
0225
0225 RAMP 3
70 Sec
Ramp 3: Slow acceleration time
Possible settings: 1 – 250 sec
o A too fast running up time may lead to oscillation and/or an error (OVERLOAD).
o A too slow running up time can cause a drop of the outgoing pressure during variation
of the demand.
0230
0230 RAMP 4
70 Sec
Ramp 4: Slow deceleration time
Possible settings: 1 – 250 sec
o A too fast running down time leads to oscillation of the HYDROVAR and thereby of the
pump.
o A too slow running down time can cause pressure fluctuations during variation of the
demand.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ITT HYDROVAR Series and is the answer not in the manual?

ITT HYDROVAR Series Specifications

General IconGeneral
BrandITT
ModelHYDROVAR Series
CategoryControl Unit
LanguageEnglish

Related product manuals