72
0430
0430 SENS 1 CAL0
0% = 00.00 bar
Sensor 1 zero value calibration
Possible settings: - 10% up to +10% of the sensor range
This parameter is used to calibrate the minimum value of Sensor 1.
After setting the Dimension Unit and the Sensor range the minimum value for this sensor
can be adjusted. Adjustable range between -10 % and +10 % of the Sensor Range.
e.g. DIMENS. UNIT [0405] = bar
SENS. RANGE [0420] = 10.00 bar
SENS 1 CAL0 [0430] = 2% -> 00,20 bar
0435
0435 SENS 1 CALx
0% = 10.00 bar
Sensor 1 full value calibration
Possible settings: - 10% up to +10% of the sensor range
To set the calibration for the maximum value of Sensor 1, this parameter can be used. After
setting the right Dimension Unit and Sensor range the maximum value can be adjusted
between -10 and +10% of the Sensor Range.
e.g. DIMENS. UNIT [0405] = bar
SENS. RANGE [0420] = 10.00 bar
SENS 1 CAL0 [0430] = -2% -> 09,80 bar
0440
0440 SENS 2 CAL0
0% = 00.00 bar
Sensor 2 zero value calibration
Possible settings: - 10% up to +10% of the sensor range
Zero value calibration for Sensor 2, for explanation see Parameter 0430.
0445
0445 SENS 2 CALx
0% = 10.00 bar
Sensor 2 full value calibration
Possible settings: - 10% up to +10% of the sensor range
Full value calibration for Sensor 2, for explanation see Parameter 0435.