Page 58 = Key 1 = Key 2 = Key 3= Maximum or consumption = Minimum or supply.
Set function = oFF
The tariff changeover is carried
out by the internal time program
"z".
For devices with the auxiliary voltage of "85 .. 265VAC,
120 .. 370VDC" the auxiliary input is activated with an
alternating voltage of 85 .. 265VAC .
CONF
For devices with an auxiliary voltage of "15 .. 55VAC, 20
.. 80VDC" the auxiliary input is activated with an alter-
nating voltage of 15 .. 55VAC or a direct current
voltage of 20 .. 80VDC.
For devices with an auxiliary voltage of "40.. 115VAC,
55.. 165VDC" the auxiliary input is activated with an
alternating voltage of 40.. 115VAC or a direct current
voltage of 55.. 165VDC.
Symbol text for the au-
xiliary input
Diagr.: Auxiliary for direct current and alternating volta-
ge
Diagr.: Auxiliary voltage for alternating voltage only
Select
In menu CONF move
to the indication of au-
xiliary input using key
3
EDIT CONF
Change
Confirm with key 1.
The set function appears
and can be changed
with key 3.
The text EDIT appears.
If the function for the auxiliary input is set, press key 1 as
often as no digit is flashing any longer. EDIT disappears.
.
With key 3 you move to the next menu point. The function
is stored.
Programming
The external digital inputs can only be indicated and
programmed, if the protocol "06" (Modbus RTU Master)
is set at the UMG503.
The functions
- Reset real power EMAX,
- Tariff changeover and
- Synchronization of internal clock
can be programmed according to the table "assignment
of auxiliary inputs" on page 50.
Attention!
The wiring for the auxiliary input must be suitable for
voltages up to 300VAC against ground.
On the internal auxiliary input,
only the tariff changeover is ac-
tive.
UMG503
AC/DC