Page 59= Key 1 = Key 2 = Key 3 = Maximum or consumption = Minimum or supply
Tariff change over
For energy measurement, which should be carried out in
certain periods, four tariffs are available:
T01 .. T04 Real energy consumption and real power
EMAX,
T11 .. T14 Reactive energy, inductive and
T21 .. T24 Reactive energy, capacitive.
The tariff changeover is carried out internally via a time
program or externally via the auxiliary input. To each of
the three tariff groups T0x, T1x and T2x 10 changeover
times can be assigned.
Work meter Tx0 is not programmable.
External tariff change over (option)
The first two work meters can be changed over via the
auxiliary input.
When the contact is open, work meter Tx2 is active.
When there is voltage on the auxiliary input, work meter
Tx1 is active.
When the auxiliary input is programmed for tariff change
over, only the work meters Tx3 and Tx4 can be cont-
rolled via the time program.
Attention!
The energy meters (Tariffs) cannot be deleted
individually. If reactive or real energy is deleted,
all corresponding energy meters (tariffs) are de-
leted.
Energy meter
Controlled via
Internal time program
Auxiliary input
Real energy
Without reverse running stop T50
Consumption, real power EMAX T00 T01 T02 T03 T04
Supply T30
Reactive energy
Without reverse running stop T40
inductive T10 T11 T12 T13 T14
capacitive T20 T21 T22 T23 T24
Wh
D.H
M.S
L1
L2
L3
CONF
T
Changeover time
Symbol Number
Starting
time:
-Hour
-Second
-Minute
Sum
Energy meter
Symbol Energy type Number
Real energy
Consump-
tion
Week day
- beginning
- end