3-4
SM-18006
TROUBLESHOOTING
Table 3.1 Electrical Characteristics and Recommended Wiring Size
NOTICE:
1. Select wire size based on the value of MCA.
2. MOP is used to select the fuse, circuit breaker, or a Ground Fault Circuit Interrupter (GFCI).
3. Communication cabling shall be a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper. Shielded
cable must be considered for applications and routing in areas of high EMI and other sources of potentially
excessive electrical noise to reduce the potential for communication errors. When shielded cabling is applied,
proper bonding and termination of the cable shield is required as per Johnson Controls guidelines. Plenum and
riser ratings for communication cables must be considered per application and local code requirements.
208/230V
Model
Water Source Unit Inverter 1 Inverter 2 Fan Motor 1
Hz Voltage Max. Min. MCA MOP Max. Fuse MOC MOC FRA
(Hz) (V) (V) (V) (A) (A) (A) (A) (A) (A)
(H,Y)VWH(P,R)072B32S 60 208/230 253 188 20/18 30/30 30/30 15.4/14.0 - 0.08
(H,Y)VWH(P,R)096B32S 60 208/230 253 188 32/29 50/45 50/45 25.0/22.7 - 0.08
(H,Y)VWH(P,R)120B32S 60 208/230 253 188 38/34 60/50 60/50 29.8/27.0 - 0.08
(H,Y)VWH(P,R)144B32S 60 208/230 253 188 37/34 50/45 50/45 16.4/14.8 16.4/14.8 0.08
(H,Y)VWH(P,R)168B32S 60 208/230 253 188 41/37 50/50 50/50 18.0/16.4 18.0/16.4 0.08
(H,Y)VWH(P,R)192B32S 60 208/230 253 188 55/50 70/60 70/60 24.3/22.0 24.3/22.0 0.08
(H,Y)VWH(P,R)216B32S 60 208/230 253 188 71/64 90/80 90/80 31.2/28.3 31.2/28.3 0.08
Model
INV Comp. 1 INV Comp. 2 Fan Motor 1 Wiring Size
LRA LRA Output
Power Supply
Wiring
Ground
Wiring
Communication
Cable
(A) (A) (kW) (AWG) (AWG) (AWG)
(H,Y)VWH(P,R)072B32S 54 - 0.016 14/14 14/14 18
(H,Y)VWH(P,R)096B32S 54 - 0.016 10/10 10/10 18
(H,Y)VWH(P,R)120B32S 50 - 0.016 8/8 8/8 18
(H,Y)VWH(P,R)144B32S 54 54 0.016 8/8 8/8 18
(H,Y)VWH(P,R)168B32S 54 54 0.016 8/8 8/8 18
(H,Y)VWH(P,R)192B32S 54 54 0.016 6/6 6/6 18
(H,Y)VWH(P,R)216B32S 54 54 0.016 4/4 4/4 18
460V
Model
Water Source Unit Inverter 1 Inverter 2 Fan Motor 1
Hz Voltage Max. Min. MCA MOP Max. Fuse MOC MOC FRA
(Hz) (V) (V) (V) (A) (A) (A) (A) (A) (A)
(H,Y)VWH(P,R)072B42S 60 460 506 414 11 15 15 8.0 - 0.08
(H,Y)VWH(P,R)096B42S 60 460 506 414 17 25 25 13.0 - 0.08
(H,Y)VWH(P,R)120B42S 60 460 506 414 20 30 30 15.5 - 0.08
(H,Y)VWH(P,R)144B42S 60 460 506 414 20 25 25 8.5 8.5 0.08
(H,Y)VWH(P,R)168B42S 60 460 506 414 22 25 25 9.4 9.4 0.08
(H,Y)VWH(P,R)192B42S 60 460 506 414 29 40 40 12.7 12.7 0.08
(H,Y)VWH(P,R)216B42S 60 460 506 414 37 50 50 16.3 16.3 0.08
Model
INV Comp. 1 INV Comp. 2 Fan Motor 1 Wiring Size
LRA LRA Output
Power Supply
Wiring
Ground
Wiring
Communication
Cable
(A) (A) (kW) (AWG) (AWG) (AWG)
(H,Y)VWH(P,R)072B42S 47 - 0.016 18 18 18
(H,Y)VWH(P,R)096B42S 47 - 0.016 14 14 18
(H,Y)VWH(P,R)120B42S 47 - 0.016 12 12 18
(H,Y)VWH(P,R)144B42S 47 47 0.016 12 12 18
(H,Y)VWH(P,R)168B42S 47 47 0.016 12 12 18
(H,Y)VWH(P,R)192B42S 47 47 0.016 10 10 18
(H,Y)VWH(P,R)216B42S 47 47 0.016 8 8 18
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
MOC: Maximum Operating Current (A)
LRA: Locked Rotor Ampacity (A)
FRA: Fan Motor Running Ampacity (A)