EasyManua.ls Logo

Johnson Controls HVWHP072B32S - Page 25

Johnson Controls HVWHP072B32S
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SM-18006
3-5
TROUBLESHOOTING
Install a multi-pole main switch with a space of 1/8 inch (3.5mm) or more between each phase.
Do not connect the ground wiring to gas piping, water piping, or a lighting conductor.
Gas Piping: An explosion and ignition may occur if there is escaping gas.
Water Piping: There is no effective electrical ground provided when hard vinyl piping is used.
Lightning Conductor: The electrical potential of the earth increases when a lightening conductor
is used.
● Adjust wiring size when wiring runs are abnormally long.
Electrical code must be followed and total voltage drop must not exceed 2%.
● Power supply voltage should be as follow.
Supply Voltage: Rated Voltage within +10%
Starting Voltage: Rated Voltage within -15%
Operating Voltage: Rated Voltage within +10%
Imbalance between Phases: within 3%
● Wired Controller Connecting Diagram
(a) Wired Controllers to each Unit for Individual Operation Setting
(b) One Wired Controller for Individual Operation Setting
Indoor Unit Indoor Unit
A B
Water Source
Unit
A B
Wired
Controller
Wired
Controller
Indoor Unit
A B
The communication cabling
for the wired controller is
necessary.
Indoor Unit
A B
Wired
Controller
Water Source
Unit
NOTICE:
Thermo-ON: The water source unit and some indoor units are running.
Thermo-OFF: The water source unit and some indoor units stay on, but don’t run.

Table of Contents