EasyManua.ls Logo

Johnson Controls HVWHP072B32S - Page 263

Johnson Controls HVWHP072B32S
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SM-18006
5-5
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(2) BypressingPSW2orPSW4,theinput/outputterminalnameischanged.
The following shows the display changes when PSW2 or PSW4 is pushed.
(4) AfterselectingtheControlFunctionNo.,turnOFFDSW4-No.6.Thedisplaywillbebacktothenormal
operation.ThenturnOFFtheDSW4-No.4.ConrmiftheDSW4issettofactorysettings.Theselected
dataisstoredinthewatersourceunitPCBandthe“ExternalInputandOutputSetting”iscompleted.
The stored data is maintained even when the power supply is cut OFF. Refer to Table 5.1 below for
the details for the electrical wiring connection and the required parts.
If an alternative setting is required at a site, perform the following procedures.
(1) Byselecting“ExternalInputandOutputSetting”,thefollowingappearsonthe7-segmentdisplay.
(Thesettingshouldbeperformedduringanwatersourceunitstoppage.Also,setDSW4-No.4of
the water source unit PCB to the “ON” side before performing the setting in order to prevent the
compressor activation.)
This display indicates Control Function No.4 (Flow Switch Signal) is set at input 1.
SEG2 SEG1
Input/OutputTerminalName Control Function No.
(3) AfterselectingtheInput/OutputTerminalName,pressPSW3orPSW5,andthenchoosetheControl
Function No.
By pressing PSW3, the number increases by 1.
By pressing PSW5, the number decreases by 1.
(Control Function No.14
Press PSW3 return to 0)
● SettingsforExternalInputandOutput
Input Terminal
Name 1
Input Terminal
Name 2
Input Terminal
Name 3
Output Terminal
Name 1
Output Terminal
Name 2
PSW2
ON
PSW4
ON
Current setting function is indicated as
Control Function No.
(The figure is for setting at the factory.)

Table of Contents