SECTION 6 – USER INTERFACE CONTROL CENTER
DISPLAY TEXT TYPE ID VALUE RANGE LOCATION DESCRIPTION
DE Modifier
Offset
-1 to 99
Used in Combination with the DE
Modier Address to Enter A Specic
DE Instance. See Section 6 - Com-
munication
Factory Run
Tester
User Disable /
User Enable
Only Used for Factory Run Test
P1 Baud Rate
1200,
4800, 57600
9600, 19200,
38400, 76800
Establishes the Communication Baud
Rate for Port 1
P1 Manual
MAC Address
-1 to 127
Allows the Manual Entrance of the
MAC Address For Port 1. See Section
6 - Communication
P1 Parity
None, Even, Odd,
Ignore
Do not Change from Default Value for
BACNET
P1 Protocol BACNET, API Keep Setting on BACNET
P1 Stop Bits 1-2
Do not Change from Default Value for
BACNET
P2 Baud Rate
1200,
4800,
9600, 19200,
38400, 57600
Establishes the Communication Baud
Rate for Port 2
P2 Manual
MAC Address
-1 to 127
Allows the Manual Entrance of the
MAC Address for Port 2. See Section
6 - Communication
P2 Parity
None, Even, Odd,
Ignore
Establishes the Parity for Communi-
cation Port 2
P2 Protocol
Terminal, Mod-
bus I/O, Modbus
Server, API, Mod-
bus Client
Establishes the Protocol for Commu-
nication Port 2
P2 Stop Bits 1 - 2
Establishes the Stop Bit Setting for
Communication Port 2
Update Flash On / Off Used to Update Control Software
Update Flash
Error
Description of the Error
(Only Displayed when Error is Present)
TABLE 40 - SERVICE (CONT'D)