9 Parameter level
44
Active
parameter set
When parameter set 2 is active, the
decimal point on the right of display 2
lights up.
Output limiting Y1 0—100% 100% Maximum output limit
Y2 -100 to +100% -100% Minimum output limit
Minimum relay
ON time
TK1 0—60sec 0 sec Limitation of the switching rate on
switching outputs.
TK2 0—60sec 0 sec
PARAMETR ➔ PARASET1
The parameter displays on the unit depend on the controller type
that was selected.
v Section 10.1 “Controller”