for connecting a switch to earth ground. Before you begin connecting a switch to earth
ground, ensure you have the parts and tools required for your switch.
Table 59: Parts and Tools Required for Connecting an EX Series Switch to Earth Ground
Additional
InformationScrewdriver
Screws and
Washers
Grounding Lug
Specifications
Grounding Cable
Requirements
Earthing
Terminal
LocationSwitch
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—not
provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Rear panel
of the
chassis
EX2200
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—not
provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Rear panel
of the
chassis
EX2300-C
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—not
provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Rear panel
of the
chassis
EX2300
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 146.
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Rear panel
of the
chassis
EX3200
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Rear panel
of the
chassis
EX3300
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—not
provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Rear panel
of the
chassis
EX3400
Copyright © 2017, Juniper Networks, Inc.144
EX4200 Switch Hardware Guide