GB - 98
Special adjustments
No. Name r/w Enter Origin
CP.21 last error – – In.24 set 0
CP.22 last error -1 – – In.24 set 1
CP.23 last error -2 – – In.24 set 2
CP.24 last error -3 – – In.24 set 3
CP.25 last error -4 – – In.24 set 4
CP.26 last error -5 – – In.24 set 5
CP.27 last error -6 – – In.24 set 6
CP.28 last error -7 – – In.24 set 7
Parameters CP.21…CP.28 display the last eight errors. With exception error "underpotential
E.UP" is not stored. The oldest error is displayed in CP.28. A new error is stored in CP.21.
Allothererrorsareshiftedtothenextparameter.Theoldesterror(CP.28)isnotapplicable.
The meaning of the error messages is described in parameter CP.01.
No. Name r/w Enter Origin
CP.29 software version – – In.06
Value range Meaning
0.00…9.99 Displayoftheinvertersoftwareversionnumber(e.g.1,11).
No. Name r/w Enter Origin
CP.30 software date – – In.07
Value range Meaning
0…6553.5 Displayoftheinvertersoftwaredateintheformat„ddmm.y“.
No. Name r/w Enter Origin
CP.32 puls off level yes – cS.06
Value range default Meaning
0.0…-1000.0 kW -0.8 kW
If the adjusted regenerative power is decreased, the COM-
BIVERT R6-S switches the modulation off after turn-off de-
layandchangesintostandbymode(display:„Stb“).
No. Name r/w Enter Origin
CP.33 operating mode yes yes Pn.19
This parameter determines the master or slave of regenerative units at parallel connection.
Furtheritisadjustedwhetheraharmoniclteroracommutationchokeisseries-connected.
Single units must be adjusted to master.
Value range Meaning
0 Master with commutation choke
1 Masterwithharmoniclter
2 Slave with commutation choke
3 Slavewithharmoniclter