GB - 68
Technical Data
Exceeding of the max. rechargeable DC link capacity can lead to a defect.
AloadremovalintheDClinkcirclemaybedoneonlyafterthemessage„ready“.
If the control release is set when switching off the mains, this can lead to an overcurrent error and the lifetime of
the module can be reduced.
The unit must be disconnected from the supply system or the load must be switched off in case of overcurrent or
overload.
5.1 Overload (OL) function
105
110 120 130 140 150
160
100
150
200
250
270
60
Load
Release time [s]
Figure 21: Overload (OL) function
5.2 Operating conditions
Standard Standard/
class
Instructions
Denitionaccordingto
EN 61800-2 Inverterproductstandard:
ratedspecications
EN 61800-5-1 Inverterproductstandard:
general safety
Site altitude
max. 2000 m above sea level
(withsitealtitudesover1000maderatingof
1 % per 100 m must be taken into considera-
tion)
Ambient conditions during operation
further on next side