126
MA06-03-1-01
Menu
[Direct access: CMD -> 7137 -> 7142 -> 7182]
Parameter
[Direct access]
Description
Default
value
Value
Range
I:UPS Evacuation
Definition of an input for UPS which
activates the evacuation mode.
I: ET release
Definition of an input which enables an
evacuation travel. This serves to create an
evacuation chain where always only one lift
is running.
T:ET delay (s)
Determination of a delay time in seconds.
After this interval has elapsed, the
evacuation travel will be started. The
counter starts when the evacuation signal
arrives at “I:ET USV “.
0
0-999 s
Floor ET
Definition of a landing to which people are
evacuated.
0
(=deactivate
d)
0-max.
landing
O:ET active
Definition of an output to signal that the
evacuation mode is active.
O: In ET floor
Definition of an output to signal that the car
has reached the evacuation landing or has
already been there. The evacuation travel
ends thereupon.
ET prior fire case
Query whether the evacuation travel has
higher priority than the fire case.
NO
YES/NO
ET prior fire service
Query whether the evacuation travel has
higher priority than the fire case.
NO
YES/NO