Parameter
[Direct access]
When this surveilance is enabled, the
controller monitors whether the MON input
is active after the end of travel. If the
controller does not detect the input active,
the lift switches into out of order mode and
a corresponding error is reported.
NO serves to switch off the contactor pull-in
monitoring. YES activates it.
When this surveillance is enabled, the
controller monitors whether the MON input
is inactive during the travel. In case the
controller detects the input active, the lift
switches into out of order mode.
NO serves to switch off the car light
monitoring. YES activates it.
The GENIUS20 relay board checks whether a
current flow at the car light. If not, the car
light is either defective or switched off. If,
however, the car light is switched on with no
current being available in the light circuit, the
lift goes to “out of order”-mode. The display
at the hand terminal shows the error
message “Error car light”.
NO serves to switch off the alarm
monitoring. YES activates it.
The controller is equipped with an alarm
input “AL”. The alarm is triggered when the
input connects to potential “0 V”. If the
alarm signal is active for more than 5 seconds
and an emergency call system is installed, a
connection for voice communication with
the control centre will be established
automatically by means of a pre-installed
modem.
The only exception applies if the parameter
“O: Alarm Filtering” on the page for “General
outputs 2/6” is set to YES. In that case, no
connection for voice communication will be
established.
NO serves to blind out certain errors in DCP
communication. YES, serves to display it and
respond accordingly.