Parameter
[Direct access]
Query whether fast inspection travel is to be
effected at intermediate speed V1.
Query whether the V3 signal is to be put out
to reach the intermediate speed.
Selection which output serves to issue the
relevelling speed Vn.
Query to set a time frame for standstill (in
minutes) after which a warm-up drive needs
to be performed. Set a time from minimum
15 minutes to maximum one day or - by
entering value 0 - deactivate the warm-up
drive.
If this parameter is assigned with a value
larger than 0, the following parameter must
be programmed.
State the target floor for the warm-up drive.
If the lift is already standing in this landing, it
will run to the lowest (or currently opposite)
landing instead.
Enables the valve test. Once a day, at a
predefined time, the valve test is executed, if
enabled. In this case, the two valves are being
activated independently and successively in
order to check whether a car movement is
detectable. If no car movement is registered,
both valves are fully functional and the
installation remains in operation. In any
other case, the installation is put out of
operation with a “valve error”.
Indicate the hour in which the daily valve test
is to be carried out.
Query whether a run corresponding to the
warm-up run is to be conducted prior to a
valve-test. This run is intended to
compensate a possible pressure loss which
can occur after an installation’s longer
immobility.
Selection of the input to test the control
block of a hydraulic system using the RUN
signal: During standstill the RUN-signal is
turned off and reactivates within 2s after the
lift starts travelling. At the end of the travel
RUN is again deactivated within 2s.